Description:

  • Model Number (M/N): LGH120H4BH2Y
  • Serial Number (S/N): 5611E00760
  • Catalog Number (C/N): N2892

Heating Data (Chauffage):

  • Input (BTUM Max/Min): 0-2000
    • Puissance Calorifique (Brute Max/Min): 240,000/156,000
  • Input (BTUM Max/Min): 2001-4500
    • Puissance Calorifique (Brute Max/Max): 230,000/156,000
  • Output (BTUM Max): Puissance Calorifique (Brute Max): 192,000
  • Manifold Pressure (In.W.C.): 0-2000
    • Press a la Tubulure d'Alimentation (Po.C.E.): 3.7/1.6
  • Manifold Pressure (In.W.C.): 2001-4500
    • Press a la Tubulure d'Alimentation (Po.C.E.): 3.4/1.6
  • Gas Outlet Air Temp: Pression Entree (Max/Min Po.C.E.): 10.5/4.7
  • Temperature Rise: Temp. Max. D'Air de Sortie: 185°F
  • Unit Tested at Max: L'Elevation de Temperture: 40-70°F

Cooling Data (Contient du HFC-410A):

  • Factory Charge: Charge a l'Usine: Contains/Contents: MIN Designs Press/Pression
    • Stage 1: 14 lbs 8 ozs; Stage 3: Low/Basse 236 PSIG
    • Stage 2: 13 lbs 8 ozs; Stage 4: High/Haute 446 PSIG
  • Cooling BTUH: 119,500; EER: 12; Thermal Eff: 80%

Electrical Rating/Circuit Electrique:

  • Rated: Characteristic: Volts 208/230; Hertz 80; Phase 3
  • Optional 115V CKT. Rated: En Option 115V CKT. Rated: 115 Volts; 1 Phase
  • SCCR: 3000A; Min. CKT. Ampacity/Max Fuse or Ckt. Bkr: Ampérage Minimum Fusisble/Coupe Circuit

Operation Limits:

  • Volts: Min 187, Max 253; Volt Ckt. W/O Power Exhaust: Sans Évacuateur Motorisé: 46; 15; 60; 15
  • W/O Power Exhaust/Avec Évacuateur Motorisé: 46; 60
  • Motor Ratings (Qty/RLA/HP/PH/FLA/LRA):
    • Compressor(1): 13.5/3/109
    • Compressor(2): 13.5/3/109
    • Compressor(3): 13.5/3/109
    • Compressor(4): 13.5/3/109
    • Evaporator: 3/10.0
    • Outdoor Fan (Condenseur): 2/0.33/1/2.4
    • Combustion Air Blower (208/230): 1/0.5
    • Opt Exhaust (Opt Ventilateur D'Évacuation): 1/0.33/1/2.4

Minimum Ambient Temp. in Which Unit May Be Operated (Température Minimale à Laquelle L'Unité Peut Opérer):

  • -40°F Without Vestibule Heater/ - 40°C Sans Chauffe - Vestbule
  • -60°F With Vestibule Heater Kit